Application: | Three Phase Transducer |
---|---|
Output Type: | Triple |
Principle of Work: | Vector Control Transducer |
Switch Mode: | High Carrier Frequency PWM Control |
Main Circuit Type: | Voltage |
Voltage of Power Supply: | Low Voltage Variable-Frequency Drive |
Customization: |
---|
Suppliers with verified business licenses
Standard dual RS485, on-line monitoring of balance | Standard dual relay,one-drive-two rotation work |
Standard dual analog, current voltage change at random |
Online wiring simple, up to 6 units | One-key pressure setting, simple macro parameters tuning |
Single/multi point pressure detection, more accurate & efficient | Special control: dormancy, leaking, automatic recovery |
Special protection: lack of water, antifreeze, high and low pressure alarm |
Universal product design | Wide range of 0.75 ~ 400 kW power |
Stable | Open panel control function, fan pump is available |
No negative pressure water supply system | Secondary pressure water supply system |
Water treatment, circulating water system | Air conditioning hot and cold water systems |
Starting torque: | 0.5Hz 100% |
Speed adjustable range: | 1:100 |
speed-holding precision: | ±1.0% |
Overload capability: | 150% rated current for 60s; 180% rated current for 1s |
Acceleration/deceleration time: | Range: 0.01 ~ 360s |
Start frequency: | 0.01~10.00Hz |
Input voltage: | 220V/380V±15% |
Input frequency range: | 50/60Hz, fluctuation range: ±5% |
Output voltage: | 0 ~ rated input voltage |
Output frequency: | 0~50/60Hz |
Programmable digital input: | 6 ways of digital terminal input |
Programmable analog input: | AI1: 0/4 ~ 20mA; To switching 0~10V by setting parameters AI2: 0/4 ~ 20mA; To switching 0~10V by setting parameters |
Relay output: | 2 way of output, programmable |
Open-collector output: | 1 way of output, programmable |
Analog output: | Reserved |
Command running channel: | Three kinds of channels: 1. operation panel 2. control terminal 3.serial communication port, choose 1 and 2 for host drive and 3 for auxiliaries |
Multi-Pump Smart Link: | One drive in the system can be host and controls auxiliaries(4 at most) to work by communication mode. Host sends PID feedback to auxiliaries and monitors status of auxiliaries in real time. If failure occurs, the auxiliary will be skipped. |
Integrated PID: | Advanced PID arithmetic to realize closed loop control system |
AVR: | When grid voltage changes, it keeps output voltage constant automatically. By default, it doesn't work at deceleration. |
Stall control: | Automatically limit current and voltage at running period to prevent tripping caused by frequent overcurrent/overvoltage. |
Water shortage protection: | Controller detects that pipe network pressure is lower than water shortage pressure, system stops working automatically. After set period, it restarts automatically for specified times. If pressure restores to normal, system works normally. Otherwise, system stops automatically in case of idle running of pump and prolongs pump lifetime in maximum. |
High pressure alarm: | When pressure exceeds set pressure, it stops automatically to prevent pipe network from high pressure. |
Automatic energysaving running: | Decrease output voltage automatically at light load to save energy. |
Password setting: | 4-bit password can be set with non-zero numbers. Exit password setting interface and the password will be valid after 1 minute. |
Parameter lock: | Define whether the parameter is locked in running or stopped state in case of misoperation. |
Installation environment: | Installation environment should have be without direct sunlight, dust,corrosive gas, inflammable gas, oil mist, steam, water drop |
Altitude: | Lower than 1000m, service in derated capacity above 1000m. Derate 1% capacity every 100m increase in height. |
Environmental temperature: | -10ºC ~ +40ºC, service in derated capacity for 40ºC ~ 50ºC. Derate 4% capacity every 1ºC increase in temperature.B29 |
Humidity: | ≤95%RH, no water condensation |
Vibration: | <5.9m/S2 (0.6G) |